How the fuse limits are worked out
- Full-load current on each side: VA ÷ volts for a single-phase transformer, or VA ÷ (√3 × volts) for three-phase.
- Maximum fuse from NEC Table 450.3(B) for transformers 1000 V and under:
- Primary only: 125% at 9 A or more, 167% from 2 A to under 9 A, 300% under 2 A.
- Primary and secondary: primary up to 250%; secondary 125% at 9 A or more, 167% under 9 A.
- Only the 125% values may round up to the next standard rating in NEC 240.6(A) (Table 450.3(B), Note 1). All other percentages are hard limits, so you round down to an available fuse.
- Control circuit transformers (NEC 430.72(C)): when the primary current is under 2 A, (C)(4) allows primary protection up to 500%. Otherwise, protect the transformer per Article 450 as (C)(2) permits.
- Minimum fuse: the smallest rating that carries the transformer's full-load current. Anything smaller can open under normal load.
Worked example
The calculator opens with a 500 VA, 480 V to 120 V single-phase control transformer with primary fuses only.
- Primary current: 500 ÷ 480 = 1.04 A. That is under 2 A, so Table 450.3(B) allows 300%: 3.13 A. The largest ATQR rating not over that is 3 A.
- Smallest fuse that carries 1.04 A: 1-1/8 A. Any time-delay fuse from 1-1/8 A to 3 A meets the code.
- Switch the rule to NEC 430.72(C) and the primary limit rises to 500%: 5.21 A, so up to a 5 A fuse.
- With primary and secondary fuses: the primary limit is 250% (2.60 A → 2-1/2 A), and the 4.17 A secondary may be fused up to 167% (6.96 A → 6-1/4 A).
Choosing the fuse type
- Primary: use Class CC time-delay fuses designed for transformer inrush, such as the Mersen ATQR, Bussmann FNQ-R or LP-CC, or Littelfuse KLDR. Fast-acting fuses near the minimum size will often blow when the transformer is energized.
- Secondary: Class CC time-delay fuses work here too. Midget time-delay fuses (Mersen ATQ, Bussmann FNQ, Littelfuse FLQ) are common on control circuits, but they are supplementary fuses with a 10 kA interrupting rating; make sure that is acceptable for your circuit and your panel's SCCR.
- Above 30 A: Class CC tops out at 30 A, so larger transformers need Class J time-delay fuses.
Some manufacturers' fuse charts round the 167% and 300% limits up to the next fuse size. The NEC allows rounding up only on the 125% limits, so this calculator may give a size one step smaller than those charts.
This calculator covers transformer protection only. Conductor protection (NEC 240.4 and 725 / 724) and short-circuit ratings are separate checks.
Frequently asked questions
What size fuse do I need for a control transformer primary?
Divide the VA by the primary voltage to get the primary current. With primary fuses only, NEC Table 450.3(B) allows up to 300% under 2 A, 167% from 2 A to under 9 A, and 125% at 9 A or more. A 500 VA, 480 V transformer draws 1.04 A, so the primary fuse can be up to 3 A.
When can I use 500% on a control transformer primary?
NEC 430.72(C)(4) allows primary protection up to 500% when the transformer is a control circuit transformer in a motor control circuit and its rated primary current is under 2 A.
Can I round up to the next fuse size?
Only for the 125% limits in Table 450.3(B) (Note 1), which may go up to the next standard rating in NEC 240.6(A). The 167%, 250%, 300% and 500% limits are maximums, so round down to an available fuse.
What fuse should I use on a control transformer?
Use time-delay fuses that ride through the transformer's magnetizing inrush, such as Class CC Mersen ATQR, Bussmann FNQ-R or Littelfuse KLDR on the primary. Midget time-delay fuses such as the Mersen ATQ are common on the secondary where supplementary protection is acceptable.