Control panel SCCR calculator

Beta. This calculator is still being tested and may change. Check every result against the NEC, UL 508A and manufacturer data.

Find the panel's short-circuit current rating with the weakest-link method, and check it against the fault current available where the panel will be installed. You enter the ratings; this page does the bookkeeping.

Step 1. Available fault current at the panel

About this number

From the transformer, this uses the infinite-bus method: the worst case at the secondary terminals, assuming the utility can supply unlimited current. The real value at your panel is lower once conductor length is included (point-to-point method). NEC 409.22 requires the available fault current at an industrial control panel to be documented, so ask the facility engineer or utility for it when you can.

Step 2. Current-limiting feeder device (optional)

Step 3. Power-circuit components

Only power-circuit parts count. Control circuits fed from a Class 2 source or a transformer secondary don't need to be listed. Ratings are user-entered; verify each against the nameplate or the manufacturer's current SCCR tables at your voltage.

Where to find ratings
  • Breakers and fuse holders: interrupting rating (kAIC) on the nameplate or label, at your voltage.
  • Contactors, starters, drives, terminal blocks, disconnects: "SCCR" or "short-circuit current rating" in the instruction sheet or UL listing. Drives often list a different rating for each fuse or breaker type.
  • Tested combinations (e.g. a motor protector + contactor, or breaker + drive): manufacturers' high-fault SCCR tables and selection tools. Rockwell, Siemens, Schneider, Eaton and ABB all publish these; some need a free account. Enter the combination as one line.
  • Unmarked parts: UL 508A Table SB4.1 gives assumed default ratings.

Result

Panel SCCR—

Component check

ComponentListedCounts as

What SCCR means for a control panel

The short-circuit current rating (SCCR) is the highest fault current a panel can safely withstand. NEC 409.110 requires industrial control panels to be marked with it, and NEC 409.22 says a panel must not be installed where the available fault current is higher than its marked SCCR. The available fault current also has to be documented at the installation.

How the calculator finds the panel rating

  1. Available fault current. From a transformer, the worst case at the secondary terminals is transformer full-load amps × 100 ÷ %Z (the infinite-bus method). For 500 kVA at 480 V and 5.75%Z that is 601 A × 100 ÷ 5.75 ≈ 10.5 kA. Conductor length between the transformer and the panel lowers the real value.
  2. Weakest link. UL 508A Supplement SB starts from the lowest rating of any power-circuit component or overcurrent device in the panel. That lowest value is the panel's SCCR unless something raises it.
  3. Tested combinations. A manufacturer may test a group of parts together (for example a motor protector with a contactor or drive) and publish a higher combination rating. Enter the combination as one line.
  4. Current-limiting feeder protection. When the feeder device is current-limiting and its peak let-through current is at or below a branch component's rating, that component is treated as protected up to the feeder device's interrupting rating. The calculator applies this only to branch components, not to branch overcurrent devices.

Where to find the ratings