What SCCR means for a control panel
The short-circuit current rating (SCCR) is the highest fault current a panel can safely withstand. NEC 409.110 requires industrial control panels to be marked with it, and NEC 409.22 says a panel must not be installed where the available fault current is higher than its marked SCCR. The available fault current also has to be documented at the installation.
How the calculator finds the panel rating
- Available fault current. From a transformer, the worst case at the secondary terminals is transformer full-load amps × 100 ÷ %Z (the infinite-bus method). For 500 kVA at 480 V and 5.75%Z that is 601 A × 100 ÷ 5.75 ≈ 10.5 kA. Conductor length between the transformer and the panel lowers the real value.
- Weakest link. UL 508A Supplement SB starts from the lowest rating of any power-circuit component or overcurrent device in the panel. That lowest value is the panel's SCCR unless something raises it.
- Tested combinations. A manufacturer may test a group of parts together (for example a motor protector with a contactor or drive) and publish a higher combination rating. Enter the combination as one line.
- Current-limiting feeder protection. When the feeder device is current-limiting and its peak let-through current is at or below a branch component's rating, that component is treated as protected up to the feeder device's interrupting rating. The calculator applies this only to branch components, not to branch overcurrent devices.
Where to find the ratings
- Breakers and fuse holders: the interrupting rating at your voltage, on the label or in the datasheet.
- Contactors, starters, drives, terminal blocks and power distribution blocks: "SCCR" or "short-circuit current rating" in the instruction sheet or UL listing.
- High-fault combinations: the manufacturer's SCCR tables or selection tools.
- Parts with no marked rating: the default values in UL 508A Supplement SB.