PanelCalc › Motor branch and feeder breaker sizing

Motor branch and feeder breaker sizing

Beta. This calculator is still being tested and may change. Check every result against the NEC, UL 508A and manufacturer data.

Size the branch protection for each motor and the feeder breaker for the whole group, following NEC 430.52 and 430.62 with full-load currents from NEC Table 430.250 (3-phase induction motors). UL 508A Section 31 uses the same method for panels.

System

Other loads: control transformers, heaters, receptacles. Continuous loads (on 3 hours or more) are counted at 125%.

Motors

Notes on the rules used
  • Branch protection maximum = table FLC × the Table 430.52 percentage, rounded up to the next standard size (430.52(C)(1) Exception 1).
  • Feeder protection maximum = the largest branch device rating + the FLC of every other motor + other loads, rounded down (430.62(A)).
  • Overload settings use the nameplate FLA: 125% for service factor 1.15 or higher, otherwise 115% (430.32).
  • Motors on drives: follow the drive's listed branch protection, and size the drive's input conductors at 125% of its rated input current (430.122).
  • If you enter the branch device you actually used, the feeder calculation uses it instead of the maximum.

Feeder

Max feeder breaker / fuse—

Branch circuits

MotorFLCMax OCPDWire ≥OL set

How the sizing works

  1. Full-load current (FLC) comes from NEC Table 430.250 for 3-phase induction motors by horsepower and voltage, not from the nameplate. The nameplate FLA is used only for overload settings.
  2. Branch-circuit protection maximum = FLC × the NEC Table 430.52 percentage for the device type: 250% for an inverse-time breaker, 175% for a dual-element (time-delay) fuse, 300% for a non-time-delay fuse and 800% for an instantaneous-trip breaker. If that is not a standard size, 430.52(C)(1) Exception 1 allows the next larger standard size.
  3. Feeder protection maximum (430.62) = the largest branch device rating in the group + the FLC of every other motor + other loads. If that is not a standard size, round down.
  4. Overload setting (430.32) = nameplate FLA × 125% for motors with a service factor of 1.15 or higher, or a temperature rise of 40 °C or less, and 115% for all others.

Worked example

The calculator opens with a 460 V group: a 10 HP conveyor and two 5 HP conveyors on inverse-time breakers, a 3 HP exhaust fan on dual-element fuses, and 5 A of other non-continuous load.

Things to watch