How the sizing works
- Full-load current (FLC) comes from NEC Table 430.250 for 3-phase induction motors by horsepower and voltage, not from the nameplate. The nameplate FLA is used only for overload settings.
- Branch-circuit protection maximum = FLC × the NEC Table 430.52 percentage for the device type: 250% for an inverse-time breaker, 175% for a dual-element (time-delay) fuse, 300% for a non-time-delay fuse and 800% for an instantaneous-trip breaker. If that is not a standard size, 430.52(C)(1) Exception 1 allows the next larger standard size.
- Feeder protection maximum (430.62) = the largest branch device rating in the group + the FLC of every other motor + other loads. If that is not a standard size, round down.
- Overload setting (430.32) = nameplate FLA × 125% for motors with a service factor of 1.15 or higher, or a temperature rise of 40 °C or less, and 115% for all others.
Worked example
The calculator opens with a 460 V group: a 10 HP conveyor and two 5 HP conveyors on inverse-time breakers, a 3 HP exhaust fan on dual-element fuses, and 5 A of other non-continuous load.
- 10 HP: FLC 14 A × 250% = 35 A → 35 A breaker.
- 5 HP: FLC 7.6 A × 250% = 19 A → 20 A breaker each.
- 3 HP: FLC 4.8 A × 175% = 8.4 A → 10 A fuse.
- Feeder: 35 A (largest branch device) + 7.6 + 7.6 + 4.8 A (other motors) + 5 A (other loads) = 60 A → 60 A maximum.
Things to watch
- Motors on drives use the branch protection the drive manufacturer lists, and the drive's input conductors are sized at 125% of its rated input current (430.122).
- The feeder rule gives a maximum. A smaller feeder device is fine as long as it carries the load and the motors start.
- For an industrial control panel, UL 508A uses the same approach for branch and feeder protection. Check the edition your shop is listed to.