How the heat load is calculated
A sealed enclosure has to get rid of the heat its components make, plus any heat the room or the sun push in through the walls. The calculator works it out in four steps.
- Heat made inside the panel. Add the losses of everything inside: drives, power supplies, transformers, servo amplifiers and anything else with a meaningful loss. Transformer and power supply losses fill in from manufacturer datasheets at full rated load. Everything else comes from your datasheets.
- Heat through the walls. Qwalls = k × A × (Tambient − Tinside). A is the area of the surfaces exposed to free air: every face you have not ticked as blocked by a wall, the floor or another enclosure. When the room is cooler than the inside limit this number is negative, which means the walls shed heat for you.
- Heat from the sun (outdoor panels only). Sunlit faces are treated as if the air next to them were hotter, using the sol-air method: Qsun = k × Asunlit × absorptance × solar intensity ÷ 17 W/m²·K. A white or light gray enclosure absorbs far less than a dark one.
- Cooling needed = heat made inside + Qwalls + Qsun. If the total is zero or less, the walls alone keep the panel below your limit and no fan or air conditioner is needed.
Heat transfer coefficient (k) by enclosure material
| Material | k (W/m²·K) |
|---|---|
| Painted sheet steel | 5.5 |
| Stainless steel | 3.7 |
| Aluminum | 12 |
| Aluminum, double-walled | 4.5 |
| Polycarbonate, fiberglass or other plastic | 3.5 |
Sizing the cooling
- Filter fan. Airflow (m³/h) = 3.1 × cooling watts ÷ (Tinside − Tambient in K). In imperial units that is about CFM = 3.28 × watts ÷ ΔT in °F. A fan only works when the room is cooler than the inside limit, and the colder the room, the less air you need.
- Air-to-air heat exchanger. Look for a unit whose specific rating (W/K or W/°F) is at least cooling watts ÷ ΔT. It keeps the enclosure sealed, which matters for dusty or wet areas.
- Air conditioner. Size it for the cooling watts or BTU/h directly. It is the only option when the room can be as hot as, or hotter than, your inside limit.
Worked example
The calculator opens with this example: a 72 × 36 × 12 in painted steel enclosure mounted on a wall, so the back is ticked as not transferring heat. The inside limit is 104 °F and the room reaches 95 °F, a difference of 9 °F (5 K). Inside are a drive losing 340 W, a 24 V DC, 20 A power supply (38 W) and a 1,000 VA open-core control transformer (69.1 W).
- Heat made inside: 340 + 38 + 69.1 = 447 W (1,526 BTU/h).
- Exposed area: top and bottom 36 × 12 in each, front 72 × 36 in, two sides 72 × 12 in each = 5,184 in² = 3.34 m² (36 ft²).
- Walls: 5.5 × 3.34 × (35 − 40 °C) = −92 W, so the walls shed 92 W.
- Cooling needed: 447 − 92 = 355 W (1,212 BTU/h).
- Filter fan: 3.1 × 355 ÷ 5 = 220 m³/h, about 130 CFM, measured with the filter fitted.
Left sealed with no cooling, the inside would settle around 139 °F (59 °C), well above the 104 °F limit.
Practical tips
- Check fan ratings with the filter installed. Filter mats and exhaust grilles often cut free-air flow by 30–50%.
- Blow air in low and exhaust high. Put the filter fan near the bottom and the exhaust grille near the top on the opposite side, so cool air sweeps past the components on its way up.
- Mind the enclosure rating. Filter fans and grilles change the enclosure's NEMA or IP rating. Use parts rated for the same type, or a heat exchanger or air conditioner if the panel has to stay sealed.
- Shade outdoor panels. A sun shield removes most of the solar load; untick the faces it covers.
- Think about cold weather too. Panels with air conditioners or outdoor panels can collect condensation. Tick "Size a panel heater" to size a heater that keeps the inside above a minimum temperature.
Frequently asked questions
How do I calculate the heat load of a control panel?
Add the heat losses of the components inside (drives, power supplies, transformers and so on), then add or subtract the heat that flows through the enclosure walls: k × exposed area × (ambient − allowed inside temperature). Add solar gain for outdoor panels. A positive total is the cooling the panel needs.
How much heat does a VFD give off?
At full load a drive typically loses about 2–4% of its rated power as heat, and small drives lose more. A 15 HP (11 kW) drive gives off roughly 250–450 W. The drive's manual lists the exact watts loss for each frame size; use that figure when you have it.
Should I use a filter fan or an air conditioner?
A filter fan only works when the room stays cooler than the maximum temperature allowed inside the panel. If the panel must stay sealed against dust or washdown and the room is still cooler than that limit, use an air-to-air heat exchanger. If the room can get as hot as the limit, use an air conditioner.
How do I convert watts to BTU/h?
Multiply watts by 3.412. For example, 355 W of cooling is about 1,212 BTU/h.
What surface area should I use for an enclosure?
Use only the surfaces open to free air. A face mounted against a wall, sitting on the floor or bolted to another enclosure transfers little heat, so tick it as not transferring heat.